1. Enter values
Use consistent units and the requested inputs.
Country-neutral calculator for Darcy-Weisbach Pipe Akisi Analysis - Chiller Kondanser Line Surtunme Load Loss. Major friction head loss: h_f = f_D × (L/D) × v²/(2g), using Darcy friction factor f_D, not Fanning friction factor. Distributed straight-pipe losses only. Minor losses, fittings, valves and elevation changes are excluded; f_D must match the flow regime.
Use consistent units and the requested inputs.
Use the main result and breakdowns as a planning estimate.
For regulated topics, verify current local rules before acting.
Major friction head loss: h_f = f_D × (L/D) × v²/(2g), using Darcy friction factor f_D, not Fanning friction factor.
With flow = 18, diameter = 80, length = 60, friction = 0.022, the result is 0.832402874 m.
Major friction head loss: h_f = f_D × (L/D) × v²/(2g), using Darcy friction factor f_D, not Fanning friction factor.
Distributed straight-pipe losses only. Minor losses, fittings, valves and elevation changes are excluded; f_D must match the flow regime.
Review the values and units used by this calculator before calculating.